The selection of inverter capacity is a crucial and complex task that requires careful consideration. It involves matching the inverter’s capacity with the motor’s requirements to ensure optimal performance, prevent damage, and avoid unnecessary costs. An undersized inverter can lead to reduced motor torque, system instability, and even equipment failure. Additionally, it may increase harmonic distortion, which can further raise equipment costs.
**Principles for Inverter Capacity Selection**
1. **Matching Principle**
The inverter must be compatible with the load characteristics. This includes:
- **Power Matching**: The inverter’s rated power should align with the motor’s rated power. However, different load types (e.g., constant torque vs. variable torque) require different inverter capacities. For example, a fan (square torque load) typically needs a smaller inverter than a conveyor belt (constant torque load).
- **Voltage Matching**: The inverter’s rated voltage should match the motor’s rated voltage.
- **Current Matching**: For standard loads like centrifugal pumps, the inverter’s rated current should match the motor’s. For special applications, such as deep well pumps, the inverter must account for peak currents and overload capabilities.
- **Torque Matching**: Essential when using constant torque loads or gearboxes.
2. **Economic Consideration**
A balance between technical performance and cost-effectiveness is essential. The chosen inverter should meet the application needs while offering the best value for money.
3. **Site-Specific Analysis**
Different environments and applications require tailored solutions. Factors such as load type, operating conditions, and motor specifications must be considered during the selection process.
**Steps for Inverter Capacity Selection**
1. Understand the nature of the load and its current profile (I=f(t)).
2. Pre-select an inverter based on these parameters.
3. Validate the pre-selected inverter by checking its overload and starting capabilities. If it meets all criteria, proceed; otherwise, re-evaluate.
Choosing a smaller inverter that still meets the system requirements is more economical, provided it doesn’t compromise performance.
**Common Selection Methods**
1. **From the Current Perspective**
The rated current of the inverter is a key factor in determining its load-handling capability. It’s important to ensure that the load current does not exceed this limit. For example, submersible pumps or wound rotor motors may have higher rated currents than standard squirrel cage motors, requiring a larger inverter.
2. **From the Efficiency Perspective**
System efficiency depends on both the inverter and the motor. To maximize efficiency:
- Match the inverter power to the motor power as closely as possible.
- Choose a slightly larger inverter if the motor frequently starts or operates under heavy load.
- Adjust energy-saving settings if the motor has excess capacity.
- Ensure that the inverter and motor are both operating at high efficiency levels.
3. **From the Power Calculation Perspective**
For continuous operation, the inverter must satisfy three key formulas:
- PCN ≥ PM / η (to meet load output)
- PCN ≥ k × 3 × Ue × Ie × 10â»Â³ (to meet motor capacity)
- ICN ≥ k × Ie (to meet motor current)
Where PCN is the inverter capacity (kVA), PM is the motor output power (kW), Ue is the motor voltage (V), Ie is the motor current (A), η is motor efficiency (~0.85), cosφ is the power factor (~0.75), and k is the waveform compensation factor (typically 1.05–1.1).
In summary, selecting the right inverter capacity is a multi-faceted process that considers technical, economic, and environmental factors. Proper selection ensures reliable operation, reduces energy consumption, and extends equipment lifespan.